[Recalled] Trane Voyager Series Combination Gas Furnace and Electric Air Conditioning Units — The Voyager series of light commercial rooftop air conditioners with electric c… | CPSC 2001-01-24
Authorities recorded a safety problem with this product. The details below come directly from the government recall notice.
Recall details
| Product | Trane Voyager Series Combination Gas Furnace and Electric Air Conditioning Units |
|---|---|
| Brand / manufacturer | The Trane Company, of Tyler, Texas, a division of American Standard Companies Inc. |
| Category | consumer_product |
| Issuing authority | CPSC |
| Reference | 01507 |
| Country of notice | United States |
| Hazard type | recall |
| Notice date | 24 January 2001 |
Why it was recalled
According to the CPSC notice, the identified hazard is: The Voyager series of light commercial rooftop air conditioners with electric cooling and gas-fired heat exchangers, which are installed in schools and commercial applications, have 120,000 to 135,00 BTU heating capacity and three- to five-ton cooling capacity in horizontal and downflow configurations. The Voyager series has been manufactured by Trane since 1988 and is distributed under the Trane® and American Standard® brand names. The recalled units were manufactured between June 1, 2000 and August 16, 2000 and have serial numbers beginning with R21 through and including R33. The recalled products include the following model designations: YCD036C1H_ _ _ YCD060CWH_ _ _ YCD048C1H_ _ _ YCH060C1H_ _ _ YCH048C1H_ _ _ YCH060C3H_ _ _ YCD060C1H_ _ _ YCH060C4H_ _ _ YCD060C1H_ _ _ YCD060C3H_ _ _ YCD060C4H_ _ _ A name plate bearing each unit's model and serial number is located on the outside sheet metal at the end of the unit where the propeller fan is visible on top, directly to the left of the exposed outdoor coils. Hazards: One of the three internal flue gas tubes extending from the heat exchanger can separate from the heat exchanger. This could allow flue gases, including carbon monoxide, to enter the building airstream. This could result in serious injury or death to building occupants.
This safety recall concerns consumer_product products distributed in United States and was recorded by CPSC. Recalls in this category are published so that owners, retailers, and importers can identify affected units and act quickly.
What to do if you own this product
Review the official notice to confirm whether your unit is affected.
Read the full official notice →
This page indexes a public government recall notice for reference. We do not sell or verify this product; always confirm the current status on the authority's official site.