Reported risk: This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected. Hazards: When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Verify each fact at the issuing agency before acting. Recall scope, affected lots, and remediation instructions may be updated by the agency after our last sync.
ProductGuru indexes recall and safety-alert records from ~30 public agency registries. We are not lawyers, regulators or product-safety consultants. This page restates what the named agency published; consult the primary source above (or qualified counsel in your jurisdiction) before any commercial, medical or safety decision.